Cable types:
Build your quote | |||||
|
Fixed Wiring and Mains Cables - Stranded plain annealed compacted circular copper conductors, XLPE insulated, semi-conducting tape insulated, each core copper tape screened, low smoke and zero halogen (LSZH) bedding, galvanised steel wire armour, low smoke and zero halogen (LSZH) outer sheath - Red. 6350/11000 volts grade to BS7835. Acid gas emission to BS EN 50267 (IEC60754), smoke emission to BS EN 50268 (IEC61034) and flame propagation to BS EN 50265, BS EN 50266 (IEC 60332) . Due to poor U.V resistant qualities red outer sheath cables are not recommended for outdoor installation.
| CCC Code | Conductor size (MM2) |
Stranding | Cores | Weight (KG/KM) |
Overall Diameter (MM) |
Gland Size |
Cleat | Trefoil Cleat |
|---|---|---|---|---|---|---|---|---|
| 10302RD | 35 | 19/1.53 | 3 | 4900 | 51.6 | 50 | R9 | - |
| 10304RD | 50 | 19/1.78 | 3 | 5600 | 54.6 | 63S | R9 | - |
| 10306RD | 70 | 19/2.14 | 3 | 6500 | 58.5 | 63S | R10 | - |
| 10308RD | 95 | 19/2.52 | 3 | 7800 | 62.6 | 63 | R10 | - |
| 10310RD | 120 | 37/2.03 | 3 | 8900 | 66.6 | 75S | R11 | - |
| 10312RD | 150 | 37/2.25 | 3 | 10000 | 68.8 | 75 | R11 | - |
| 10314RD | 185 | 37/2.52 | 3 | 11600 | 74.1 | 75 | R12 | - |
| 10316RD | 240 | 61/2.25 | 3 | 14800 | 81.2 | 90 | R14 | - |
| 10318RD | 300 | 61/2.52 | 3 | 17300 | 86.8 | 90 | R15 | - |
| 10320RD | 400 | 70/3.15 | 3 | 19300 | 90.9 | - | R15 | - |
Temperature limits : up to 90oc |
|