4.g - Paper Insulated, BS6480 Mains, three core, SWA, PVC, 11000V 25mm to 400mm

Fixed Wiring and Mains Cables - Plain annealed copper conductors, paper insulated, paper belted, semi-conducting carbon paper bedding, lead sheathed, textile compound bedding, galvanised steel wire armour, PVC outer sheath - Red. 6350/11000 volts grade to BS6480/88. Flame propagation to BS EN 60332. Red outer sheath can be prone to fading when exposed to UV rays.

Choose a cable type
CCC Code Conductor size
(MM2)
Stranding Cores Weight
(KG/KM)
Overall
Diameter (MM)
Gland
Size
Cleat Trefoil
Cleat
PILC3X25RD257/2.143523043.6-1.8-
PILC3X35RD3519/1.533589042.3-2-
PILC3X50RD5019/1.783662045.6-2-
PILC3X70RD7019/2.143782049.7-2-
PILC3X95RD9519/2.523924053.3-TC9-
10100RD9519/2.523711553.2-TC9-
PILC3X120RD12037/2.0331040056.2-TC9-
PILC3X150RD15037/2.2531177059.2-TC10-
PILC3X185RD18537/2.5231355062.8-TC10-
10103RD18537/2.523952163.5-TC11-
PILC3X240RD24061/2.2531639067.8-TC11-
PILC3X300RD30061/2.5231987073.6-TC12-
10105RD30061/2.5231340371.5-TC12-
PILC3X400RD40061/2.8532370079.4-TC14-

Technical Information


Temperature limits : up to 65oc.

Bending radius : 13 x overall diameter.

Core identification
: White printed numbers on insulating papers.

Should not be installed at temperatures below 0oc or above + 60oc.