25/44KV MDPE RAILWAY POWER TRANSMISSION CABLES - NR/PS/ELP/00008

25/44 KV Rail Cable - MDPE

Cable Specification : Annealed round stranded compacted copper conductor class 2 BE EN 60228, semiconductive tape applied, helically with overlap, conductor non-metallic extruded screen. XLPE type GP8 insulation to BS 7655-1.3, extruded semiconducting non-metallic core screen, semiconductive tape applied helically with overlap, copper wire metallic screen applied helically over the core and wrapped with a copper tape(83mm), MDPE,black outer sheath with graphite coating. Rated at 25/44 (52) kv. To NR/PS/ELP/00008

  • Technical
  • Products
  • Downloads

SINGLE CORE MDPE SHEATHED 25/44KV RAIL CABLE

Purpose: The 25/44kv cables are for use on 25-0-25kv auto transformer systems. The cables are designed to supply power to DC and AC line applications.

Standards: NR/PS/ELP/00008

Conductor: Stranded Plain Annealed Circular Compacted Copper Conductors

Insulation: XLPE

Bedding: Extruded semiconducting compound strippable

Screen: Copper wires helically applied over core and wrapped with a copper tape of 0.1 mm nominal thickness laid in open helix (83mm)

Sheath: MDPE

Sheath Colour: Black

Voltage Rating: 25/44kv

Temperature limits: up to 90°C

Minimum Bending Radius: As Per Manufacturers Datasheet.

Should not be installed at temperatures below 0°C or above +60°C

CCC_Code Rail Code Conductor Size(mm) No of Cores Weight(Kg/Km) Overall Diameter(mm)
25KVXLPE1X120BK
1X120MM CU/XLPE/CWS83/MDPE+GRAPHITE 25/44KV 006/148035 NR/PS/ELP/00008
Rail Code: 006/148035 Conductor Size(mm): 120 No of Cores: 1 Weight(Kg/Km): 3300 Overall Diameter(mm): 50
1X120MM CU/XLPE/CWS83/MDPE+GRAPHITE 25/44KV 006/148035 NR/PS/ELP/00008
25KVXLPE1X400BK
1X400MM CU/XLPE/CWS83/MDPE+GRAPHITE 25/44KV 006/148030 NR/PS/ELP/00008
Rail Code: 006/148030 Conductor Size(mm): 400 No of Cores: 1 Weight(Kg/Km): 6400 Overall Diameter(mm): 62
1X400MM CU/XLPE/CWS83/MDPE+GRAPHITE 25/44KV 006/148030 NR/PS/ELP/00008
25KVXLPE1X630BK
1X630MM CU/XLPE/CWS83/MDPE+GRAPHITE 25/44KV 006/148024 NR/PS/ELP/00008
Rail Code: 006/148024 Conductor Size(mm): 630 No of Cores: 1 Weight(Kg/Km): 8900 Overall Diameter(mm): 68
1X630MM CU/XLPE/CWS83/MDPE+GRAPHITE 25/44KV 006/148024 NR/PS/ELP/00008
25KVXLPE1X800BK
1X800MM CU/XLPE/CWS83/MDPE+GRAPHITE 25/44KV 006/148025 NR/PS/ELP/00008
Rail Code: 006/148025 Conductor Size(mm): 800 No of Cores: 1 Weight(Kg/Km): 11220 Overall Diameter(mm): 73.50
1X800MM CU/XLPE/CWS83/MDPE+GRAPHITE 25/44KV 006/148025 NR/PS/ELP/00008

25-44 KV Rail Cable
Last modified 04/09/2017 16:24:04


Bespoke Cable Request