Enhanced Fire Alarm Cable & Security Cable BS5839/BS7629 - 1.5mm - 4mm

FP_Enhanced

Cable Specification: Enhanced Cable Fire Alarm and Security Cable available in sizes 1.5mm to 4mm and manufactured to British Standards BS5839 and BS7629. The cable features plain annealed copper conductor, enhanced silicon rubber insulated, enhanced aluminium/polyester tape screen, tinned annealed copper earth wire, enhanced low smoke zero halogen outer sheath. Red or white. Manufactured to meet the Enhanced standard of BS5839-1 2002 +A2:2008 Clause 26.2e Enhanced and also the requirements of BS8434 - 2:2003 120 minutes and BS EN 50200 Class PH120. Fire resistant to BS7629-1:2008, BS6387:1994 clause 11 CWZ, halogen emissions to BS EN50267-2-1:1999 and low smoke standard BS EN 61034-2:2005.

  • Technical
  • Products
  • Downloads

Enhanced Cable Fire Alarm and Security Cable to BS5839/BS7629 - 1.5mm - 4mm

Purpose: Enhanced fire resistant soft skin cable is for use where a longer operating period during a fire is required. Enhanced cables can maintain circuits for up to 120 minutes upon detecting a fire. The cable features plain annealed copper conductors, silicon rubber insulation, enhanced aluminium / polyester tape screen, tinned annealed copper earth wire and a low smoke and zero halogen outer sheath in either red or white.

Standards: BS5839/BS7629, Enhanced standard of BS5839-1 2002 +A2:2008 Clause 26.2e Enhanced and also the requirements of BS8434 - 2:2003 120 minutes and BS EN 50200 Class PH120. Fire resistant to BS7629-1:2008, BS6387:1994 clause 11 CWZ, halogen emissions to BS EN50267-2-1:1999 and low smoke standard BS EN 61034-2:2005.

Conductor: Plain Annealed Copper Conductor

Insulation: Silicon Rubber

Sheath: LSZH

Sheath Colour: Red or white.

Temperature Rating: Temperature limits: -10°C to +90°C

Minimum Bending Radius: As Per Manufacturers Datasheet.

Should not be installed at temperatures below 0°C or above +40°C

For more information please consult a member of the Cleveland Cable Sales Team.

Core Identification

E = Bare Earth conductor

2 core - Brown Brown   Blue Blue  

3 core - Brown Brown   Black Black   Grey Grey  

4 core - Brown Brown   Black Black   Grey Grey   Blue Blue  

CCC_Code Conductor Size (mm2) Stranding(mm) No Of Cores Weight(Kg/Km) Overall Diameter(mm) Gland Size(mm) 1 Hole Clip Ref Gland Ref
ENH2X1/5
2C+E X 1.5 SEC CABLE ENHANCED BS5839-1-02
Conductor Size (mm2): 1.5 Stranding(mm): 1/1.38 No Of Cores: 2+E Weight(Kg/Km): 110 Overall Diameter(mm): 8 Gland Size(mm): 20 1 Hole Clip Ref: 32 Gland Ref: 251
2C+E X 1.5 SEC CABLE ENHANCED BS5839-1-02
ENH3X1/5
3C+E X 1.5 SEC CABLE ENHANCED BS5839-1-02
Conductor Size (mm2): 1.5 Stranding(mm): 1/1.38 No Of Cores: 3+E Weight(Kg/Km): 130 Overall Diameter(mm): 8.4 Gland Size(mm): 20 1 Hole Clip Ref: 34 Gland Ref: 251
3C+E X 1.5 SEC CABLE ENHANCED BS5839-1-02
ENH4X1/5
4C+E X 1.5 SEC CABLE ENHANCED BS5839-1-02
Conductor Size (mm2): 1.5 Stranding(mm): 1/1.38 No Of Cores: 4+E Weight(Kg/Km): 160 Overall Diameter(mm): 9.5 Gland Size(mm): 20 1 Hole Clip Ref: 37 Gland Ref: 251
4C+E X 1.5 SEC CABLE ENHANCED BS5839-1-02
ENH2X2/5
2C+E X 2.5 SEC CABLE ENHANCED BS5839-1-02
Conductor Size (mm2): 2.5 Stranding(mm): 1/1.78 No Of Cores: 2+E Weight(Kg/Km): 160 Overall Diameter(mm): 9 Gland Size(mm): 20 1 Hole Clip Ref: 34 Gland Ref: 252
2C+E X 2.5 SEC CABLE ENHANCED BS5839-1-02
ENH3X2/5
3C+E X 2.5 SEC CABLE ENHANCED BS5839-1-02
Conductor Size (mm2): 2.5 Stranding(mm): 1/1.78 No Of Cores: 3+E Weight(Kg/Km): 200 Overall Diameter(mm): 10.5 Gland Size(mm): 20 1 Hole Clip Ref: 40 Gland Ref: 252
3C+E X 2.5 SEC CABLE ENHANCED BS5839-1-02
ENH4X2/5
4C+E X 2.5 SEC CABLE ENHANCED BS5839-1-02
Conductor Size (mm2): 2.5 Stranding(mm): 1/1.78 No Of Cores: 4+E Weight(Kg/Km): 250 Overall Diameter(mm): 11.7 Gland Size(mm): 20 1 Hole Clip Ref: 43 Gland Ref: 252
4C+E X 2.5 SEC CABLE ENHANCED BS5839-1-02
ENH2X4
2C+E X 4 SEC CABLE ENHANCED BS5839-1-02
Conductor Size (mm2): 4 Stranding(mm): 7/0.85 No Of Cores: 2+E Weight(Kg/Km): 260 Overall Diameter(mm): 11.3 Gland Size(mm): 20 1 Hole Clip Ref: 43 Gland Ref: 252
2C+E X 4 SEC CABLE ENHANCED BS5839-1-02
ENH3X4
3C+E X 4 SEC CABLE ENHANCED BS5839-1-02
Conductor Size (mm2): 4 Stranding(mm): 7/0.85 No Of Cores: 3+E Weight(Kg/Km): 315 Overall Diameter(mm): 12.1 Gland Size(mm): 25 1 Hole Clip Ref: 47 Gland Ref: 254
3C+E X 4 SEC CABLE ENHANCED BS5839-1-02
ENH4X4
4C+E X 4 SEC CABLE ENHANCED BS5839-1-02
Conductor Size (mm2): 4 Stranding(mm): 7/0.85 No Of Cores: 4+E Weight(Kg/Km): 380 Overall Diameter(mm): 13.3 Gland Size(mm): 25 1 Hole Clip Ref: 51 Gland Ref: 254
4C+E X 4 SEC CABLE ENHANCED BS5839-1-02

Enhanced Fire Alarm and Security Cable - Tech Sheet
Last modified 08/01/2019 15:49:51


Bespoke Cable Request