BS 7870 Single Core MDPE Wind Farm Cable 33kV - 70 to 630mm

33kv_Aluminium

Application Overview: Single core high voltage cable for Windfarms Suitable for power networks, underground, outdoors and installation in cable ducting. Conforms to BS 7870-4.10. More details can be found within the technical information section below.

  • Technical
  • Products
  • Downloads

BS 7870 33KV Cable Single Core MDPE Wind Farm Cable 33kV - 70 to 630mm

Standards

BS 7870-4.10

Construction

Conductor: Stranded Aluminium Conductors

Insulation: Cross Link Polyethylene (XLPE)

Tape: Semi-Conductive Water Blocking Tape

Metallic Screen: Copper Wire Screen

Separator: Copper Tape (O.H), NonConductive Water Blocking Tape

Sheath: Medium Density Polyethylene (MDPE)

Colour: Black

Characteristics

Voltage Rating: Uo/U 19KV \ 33KV 

Maximum Voltage: 36KV 

Test Voltage: 75KV 

Partial Discharge: Level with voltage 2Uo KV max. 5pC 

Temperature Limits: 

Maximum perm conductor temp: 90°C 

Maximum perm operating temp: 130°C 

Short Circuit temp: 250°C

Minimum Bending Radius: As per cable manufacturer datasheet

Should not be installed at temperatures below 0°C

For more information please consult a member of the Cleveland Cable Sales Team.

CCC_Code Conductor Size (mm2) Stranding(mm) No Of Cores Weight(Kg/Km) Overall Diameter(mm)
33KV1X70AL
1X70 AL,XLPE(TR)CWS/35 WATER BLOCKING TAPES MDPE 33KV TO BS7870 BLACK
Conductor Size (mm2): 70 Stranding(mm): 19/2.1 No Of Cores: 1 Weight(Kg/Km): 1339 Overall Diameter(mm): 36.7
1X70 AL,XLPE(TR)CWS/35 WATER BLOCKING TAPES MDPE 33KV TO BS7870 BLACK
33KV1X95AL
1X95 AL,XLPE(TR)CWS/35 WATER BLOCKING TAPES MDPE 33KV TO BS7870 BLACK
Conductor Size (mm2): 95 Stranding(mm): 19/2.47 No Of Cores: 1 Weight(Kg/Km): 1467 Overall Diameter(mm): 38.4
1X95 AL,XLPE(TR)CWS/35 WATER BLOCKING TAPES MDPE 33KV TO BS7870 BLACK
33KV1X120AL
1X120 AL,XLPE(TR)CWS/35 WATER BLOCKING TAPES MDPE 33KV TO BS7870 BLACK
Conductor Size (mm2): 120 Stranding(mm): 35/2.04 No Of Cores: 1 Weight(Kg/Km): 1584 Overall Diameter(mm): 39.8
1X120 AL,XLPE(TR)CWS/35 WATER BLOCKING TAPES MDPE 33KV TO BS7870 BLACK
33KV1X150AL
1X150 AL,XLPE(TR)CWS/35 WATER BLOCKING TAPES MDPE 33KV TO BS7870 BLACK
Conductor Size (mm2): 150 Stranding(mm): 35/2.27 No Of Cores: 1 Weight(Kg/Km): 1720 Overall Diameter(mm): 41.3
1X150 AL,XLPE(TR)CWS/35 WATER BLOCKING TAPES MDPE 33KV TO BS7870 BLACK
33KV1X185AL
1X185 AL,XLPE(TR)CWS/35 WATER BLOCKING TAPES MDPE 33KV TO BS7870 BLACK
Conductor Size (mm2): 185 Stranding(mm): 35/2.54 No Of Cores: 1 Weight(Kg/Km): 1881 Overall Diameter(mm): 43.0
1X185 AL,XLPE(TR)CWS/35 WATER BLOCKING TAPES MDPE 33KV TO BS7870 BLACK
33KV1X240AL
1X240 AL,XLPE(TR)CWS/35 WATER BLOCKING TAPES MDPE 33KV TO BS7870 BLACK
Conductor Size (mm2): 240 Stranding(mm): 35/2.91 No Of Cores: 1 Weight(Kg/Km): 2130 Overall Diameter(mm): 45.5
1X240 AL,XLPE(TR)CWS/35 WATER BLOCKING TAPES MDPE 33KV TO BS7870 BLACK
33KV1X300AL
1X300 AL,XLPE(TR)CWS/35 WATER BLOCKING TAPES MDPE 33KV TO BS7870 BLACK
Conductor Size (mm2): 300 Stranding(mm): 35/3.25 No Of Cores: 1 Weight(Kg/Km): 2381 Overall Diameter(mm): 47.8
1X300 AL,XLPE(TR)CWS/35 WATER BLOCKING TAPES MDPE 33KV TO BS7870 BLACK
33KV1X400AL
1X400 AL,XLPE(TR)CWS/35 WATER BLOCKING TAPES MDPE 33KV TO BS7870 BLACK
Conductor Size (mm2): 400 Stranding(mm): 56/2.91 No Of Cores: 1 Weight(Kg/Km): 2723 Overall Diameter(mm): 50.8
1X400 AL,XLPE(TR)CWS/35 WATER BLOCKING TAPES MDPE 33KV TO BS7870 BLACK
33KV1X500AL
1X500 AL,XLPE(TR)CWS/35 WATER BLOCKING TAPES MDPE 33KV TO BS7870 BLACK
Conductor Size (mm2): 500 Stranding(mm): 56/3.3 No Of Cores: 1 Weight(Kg/Km): 3146 Overall Diameter(mm): 54.3
1X500 AL,XLPE(TR)CWS/35 WATER BLOCKING TAPES MDPE 33KV TO BS7870 BLACK
33KV1X630AL
1X630 AL,XLPE(TR)CWS/35 WATER BLOCKING TAPES MDPE 33KV TO BS7870 BLACK
Conductor Size (mm2): 630 Stranding(mm): 56/3.75 No Of Cores: 1 Weight(Kg/Km): 3675 Overall Diameter(mm): 58.9
1X630 AL,XLPE(TR)CWS/35 WATER BLOCKING TAPES MDPE 33KV TO BS7870 BLACK