F2 Fire Resistant Mains Cable 1kV - BS7846, BS6387, MGT, XLPE, SWA, LSZH - 1.5mm to 16mm

F2 Fire Resistant Mains Cable 1kV - BS7846, BS6387, MGT, XLPE, SWA, LSZH - 1.5mm to 16mm

Description

Fireproof Mains Cable available in sizes 1.5mm to 16mm and manufactured to British Standard BS7846 F2 / BS6387 & CWZ. The cable features plain annealed stranded copper conductor, mica fire resistant tape,thermosetting XLPE insulated, low smoke & zero halogen (LSZH) bedding, galvanised steel wire armour, low smoke & zero halogen (LSZH) outer sheath. Fire resistant to BS7846 F2 / BS6387 & CWZ. Acid gas emission to BS EN 50267 (IEC60754), smoke emission to BS EN 50268 (IEC 61034) and flame propagation to BS EN 50265, BS EN 50266 (IEC 60332-3). Suitable for fixed installations such as power circuits, fire alarm systems and emergency lighting.

Key Features
  • Installation Guidelines
    Installation Guidelines Should not be installed at temperatures below 0°C or above +40°C
  • Voltage Rating
    Voltage Rating 600/1000 Volts
  • UV/Ozone Resistance
    UV/Ozone Resistance Yes
  • Water Resistance
    Water Resistance Yes
  • Flame Retardancy
    Flame Retardancy BS EN 60332-3-24
Construction
  • Conductor: Plain Annealed Stranded Copper Conductor
  • Insulation: Cross Linked polyethylene (XLPE)
  • Bedding: LSZH (Low smoke Zero Halogen)
  • Sheath: Low smoke Zero Halogen (LSZH) to BS 7655
  • Separator: MICA/Glass Fire Barrier Tape
  • Armour: Galvanised Steel Wire Armour (SWA)
  • Sheath Colour: Black
Standards
  • Fire resistant to BS7846 F2 / BS6387 & CWZ, Acid gas emission to BS EN 50267 (IEC 60754), Smoke emission to BS EN 50268 (IEC 61034), Flame propagation: to BS EN 50265, BS EN 50266 (IEC 60332-3), BASEC Approved

Core Colours

2 core - Brown Blue
3 core - Brown Black Grey
4 core - Brown Black Grey Blue
5 core - Brown Black Grey Blue Green Yellow
** 5 cores only stocked in Coloured Cores.