F120 Enhanced Fire Resistant Mains Cable 1kV - BS7846, BS8491, MGT, XLPE, SWA, LSZH - 4mm² to 16mm²

F120 Enhanced Fire Resistant Mains Cable 1kV - BS7846, BS8491, MGT, XLPE, SWA, LSZH - 4mm² to 16mm²

Description

Fireproof mains cable, suitable for fixed installations such as power circuits, fire alarm systems and emergency lighting. Specifically designed to meet the stringent standards of BS8491, which includes enhanced resistance to heat and fire, direct impact of 10N and water jet as would be produced by a fire fighting unit.

Key Features
  • Voltage Rating
    Voltage Rating 600/1000 Volts
  • Minimum Bending Radius
    Minimum Bending Radius 8 x Overall Diameter
  • Flame Retardancy
    Flame Retardancy BS EN 60332-1-2
  • Flame Retardancy
    Flame Retardancy In accordance with IEC 60332-3-24 Cat C
  • Temperature Limits
    Temperature Limits Maximum conductor operating temperature: 90°C
    Initial temperature at S.C.C for metallic screen: 80°C
    Maximum conductor temperature during short circuit: 250°C
Construction
  • Conductor: Class 2 stranded copper conductor
  • Fire Protection: MICA Glass Fibre Tape
  • Insulation: Cross Linked polyethylene (XLPE)
  • Bedding: Low Smoke Zero Halogen (LSZH)
  • Fire Protection: MICA Glass Fibre Tape
  • Armour: Steel Wire Armour (SWA)
  • Outer Sheath: Low Smoke Zero Halogen (LSZH)
Standards
  • BS EN / IEC 60332-3-24 (cat C)
  • BS EN/IEC 60332-1-2
  • BS EN/IEC 60228
  • Fire resistant to BS7846 F120
  • LPCB Certified, BS6387 Cat CWZ

Core Colours

2 core - Brown Blue
3 core - Brown Black Grey
4 core - Brown Black Grey Blue

5 core - Brown Black Grey Blue Green Yellow

Sheath Colour Black