BS6622 Single Core Mains Cable 11kV - CU, XLPE, AWA, PVC - 50mm² to 630mm²

Description

Armoured Cable, 11KV single copper core power cable - Suitable for power networks, underground, outdoors and installation in cable ducting. Please note: the red outer sheath can be prone to fading when exposed to UV rays.

Key Features
  • Voltage Rating
    Voltage Rating 6.35/11kV Tested To Voltage And Duration of BS 6622
  • Minimum Bending Radius
    Minimum Bending Radius 15 x Overall Diameter
  • Flame Retardancy
    Flame Retardancy BS EN 60332-1-2
  • Temperature Limits
    Temperature Limits Maximum conductor operating temperature: 90°C
    Initial temperature at S.C.C for metallic screen: 80°C
    Maximum conductor temperature during short circuit: 250°C
Construction
  • Conductor: Class 2 stranded copper conductor
  • Insulation: Cross Linked polyethylene (XLPE)
  • Insulation Screen: Strippable Extruded Semi Conductor
  • Bedding: Polyvinyl Chloride (PVC)
  • Metallic Screen: Individual or overall copper tape screen
  • Separator: Copper Tape with 10% overlap
  • Armour: Aluminium Wire Armour (AWA)
  • Outer Sheath: Polyvinyl Chloride (PVC)
Standards
  • BS6622
  • IEC 60502-2
  • BS EN/IEC 60332-1-2
  • BS EN/IEC 60228

Core Colours

Sheath Colour: Red or Black

Single Core

Brown