BS7835 Single Core Armoured Power Cable 11kV - XLPE, AWA, LSZH - 50mm² to 630mm²

BS7835 Single Core Armoured Power Cable 11kV - XLPE, AWA, LSZH - 50mm² to 630mm²

Description

Medium voltage power and distribution cable, used for supply networks. The low smoke halogen free construction makes this cable ideal for use in public buildings. Please note: Red outer sheath can be prone to fading when exposed to UV rays.

Key Features
  • Voltage Rating
    Voltage Rating 6.35kV / 11kV (11kV)
    Tested To Voltage And Duration of BS7835
  • Minimum Bending Radius
    Minimum Bending Radius 15 x Overall Diameter
  • Flame Retardancy
    Flame Retardancy BS EN/IEC 60332-1
    BS EN/IEC 60332-3-24
  • Temperature Limits
    Temperature Limits Maximum conductor operating temperature: 90°C
    Initial temperature at S.C.C for metallic screen: 80°C
    Maximum conductor temperature during short circuit: 250°C
Construction
  • Conductor: Class 2 stranded copper conductor
  • Conductor Screen: Bonded semi conductive cross linked polyethylene (XLPE)
  • Insulation: Cross Linked polyethylene (XLPE)
  • Insulation Screen: Semi-Conductive (XLPE)
  • Bedding: LSZH (Low smoke Zero Halogen)
  • Metallic Screen: Copper Wire Screen
  • Separator: Copper Tape with 10% overlap
  • Armour: Aluminium Wire Armour (AWA)
  • Outer Sheath: Low Smoke Zero Halogen (LSZH)
  • Sheath Colour: Red or Black
Standards
  • BS 7835
  • IEC 61034-1
  • BS EN/IEC 60332-1-2
  • BS EN/IEC 50267-2-1
  • BS EN/IEC 60228
  • BS EN / IEC 60332-3-24
  • BS EN/IEC 60754-1

Core Colours

Brown
Electrical Data
Maximum conductor operating temperature: 90°C
Maximum screen operating temperature: 80°C
Maximum conductor temperature during S.C: 250°C
Laying Conditions At Trefoil Formation Are As Below

Soil thermal resistivity: 120˚C. Cm/Watt, Burial depth: 0.5m ,Ground temperature: 15°C ,Air temperature: 25°C, Frequency: 50Hz