Enhanced Fire Alarm & Security Cable BS5839, BS7629 - 1.5mm² to 10mm²

Enhanced Fire Alarm & Security Cable BS5839, BS7629 - 1.5mm² to 10mm²

Description

Enhanced fire alarm and security cable. Soft Skin enhanced Fire Resistant Cables for general use in fire detection, fire alarm, voice alarm, and emergency lighting circuits. Enhanced cables are designed to carry on working for 120 minutes in a fire.

The higher fire resistance this cable provides is recommended for systems in which cables might need to operate correctly during a fire for multiple phase evacuation such as tower blocks and multi storey buildings.

Note: 6mm² and 10mm² do not hold Basec, LPCB or any 3rd party accreditations

Key Features
  • Voltage Rating
    Voltage Rating 300/500 Volts
  • Minimum Bending Radius
    Minimum Bending Radius 6 x overall diameter
  • Flame Retardancy
    Flame Retardancy BS5839
  • Temperature Limits
    Temperature Limits Temperature Range: -40 to 90°C
Construction
  • Conductor: Up to 2.5mm: Class 1 solid copper, 4mm+ Class 2 stranded copper
  • Insulation: MICA/Glass tape with fire-resistant silicone rubber
  • Protective Conductor: Tinned copper
  • Overall Tape Screen: Aluminium/Polyester Tape Screen (AL/PET)
  • Outer Sheath: Low Smoke Zero Halogen (LSZH)
Standards
  • BS EN/IEC 60228
  • BS6387
  • BS 7629-1:2015 Enhanced 120
  • BS EN/IEC 61034-1/2
  • BS EN/IEC 60754-1/2

Core Colours

2 core - Brown Blue
3 core - Brown Black Grey
4 core - Brown Black Grey Blue
7 core and above - Black with White numbers
Outer sheath comes in a choice of: Red White