Nexans - BS7835 3 Core Armoured Mains Cable 11kV - CU, XLPE, SWA, LSZH - 35mm² to 400mm²

Nexans - BS7835 3 Core Armoured Mains Cable 11kV - CU, XLPE, SWA, LSZH - 35mm² to 400mm²

Description

Shop Nexans BS7835 11kV 3 core copper armoured cable, 35–400mm², with XLPE insulation, SWA and LSZH sheath for reliable power transmission.

Key Features
  • Voltage Rating
    Voltage Rating 6.35kV / 11kV (12kV)
    Tested To Voltage And Duration of BS7835
  • Minimum Bending Radius
    Minimum Bending Radius 12 x Overall Diameter
  • Flame Retardancy
    Flame Retardancy BS EN/IEC 60332-1
    BS EN/IEC 60332-3-24
  • Temperature Limits
    Temperature Limits Maximum operating temp: 90°C
    Initial temperature at S.C.C for screen: 80°C
    Maximum temp during short circuit: 250°C
Construction
  • Conductor: Class 2 stranded copper conductor
  • Insulation: Cross Linked polyethylene (XLPE)
  • Insulation Screen: Semi-Conductive XLPE
  • Filler: Polyethylene Terephthalate fibers (PET)
  • Metallic Screen: Individual copper tape screen
  • Bedding: Low Smoke Zero Halogen (LSZH)
  • Armour: Steel Wire Armour (SWA)
  • Outer Sheath: Low Smoke Zero Halogen (LSZH)
Standards
  • BS 7835
  • BS EN/IEC 60228
  • BS EN/IEC 60754-1
  • BS EN/IEC 61034

Core Colours

Brown, Black, Grey Tapes

Outer Sheath: Red or Black