N2XS(FL)H 24kV Power Cable - 35mm² to 630mm²

Description

Medium voltage power cables for fixed installations in distribution networks and for connection to process machinery, Plant and to power generation equipment. Cables can be fixed on cable trays, within conduits or fixed to walls. This cable is not suitable for direct burial.

Key Features
  • Voltage Rating
    Voltage Rating 12/20 (24kV)
  • Minimum Bending Radius
    Minimum Bending Radius 15 x Overall Diameter
  • Flame Retardancy
    Flame Retardancy BS EN/IEC 60332-1
    BS EN/IEC 60332-3-22 Cat A
  • Temperature Limits
    Temperature Limits Temperature Range: -20°C to +60°C
    Conductor Operating Temperature: +90°C
    Short Circuit Temperature up to 5 sec: 250°C
Construction
  • Conductor: Class 2 stranded copper
  • Conductor Screen: Semi-Conductive material
  • Insulation: Cross Linked polyethylene (XLPE)
  • Insulation Screen: Semi-conductive material (bonded)
  • Longditudinal Waterblocking: Semi-conductive swellable tape
  • Metallic Screen: Copper Wires plus Copper tape
  • Longditudinal Water Blocking: Swellable tapes
  • Radial Water Blocking: (Aluminium/Polyester) Tape bonded to sheath
  • Outer Sheath: Low Smoke Zero Halogen (LSZH)
  • Sheath Colour: Red or Black
Standards
  • UV Resistant Sheath
  • BS EN / IEC 60332-3-24 (cat C)
  • IEC/EN 61034-1/2,
  • IEC/EN 60754-1/2
  • BS EN/IEC 60332-1-2
  • BS EN/IEC 60228