NA2XS(FL)H 24kV Power Cable

Description
Medium voltage power cables for fixed installations in distribution networks and for connection to process machinery, Plant and to power generation equipment. Cables can be fixed on cable trays, within conduits or fixed to walls. This cable is not suitable for direct burial.
Should not be installed at temperatures below 0°C
Key Features
-
Voltage Rating 12/20 (24kV)
-
Minimum Bending Radius 15 x Overall Diameter
-
Flame Retardancy BS EN/IEC 60332-1
BS EN/IEC 60332-3-24 -
Temperature Limits Temperature Range: -5°C to +90°C
Construction
-
Conductor: Class 2 Stranded Aluminium Conductor
-
Conductor Screen: Semi-Conductive material
-
Insulation: Cross Linked polyethylene (XLPE)
-
Insulation Screen: Semi-conductive material (bonded)
-
Longditudinal Waterblocking: Semi-conductive swellable tape
-
Metallic Screen: Copper Wires plus Copper tape
-
Waterblocking Tape: Radial applied Al/PET Tape
-
Outer Sheath: Low Smoke Zero Halogen (LSZH)
Standards
-
IEC 60502-02
-
BS EN / IEC 60332-3-24 (cat C)
-
UV Resistant: EN 50396
-
IEC/EN 61034-1/2,
-
IEC/EN 60754-1/2
-
BS EN/IEC 60332-1-2
-
BS EN/IEC 60228