BS6622 3 Core Aluminium Mains Cable 11kV - STR AL, XLPE, SWA, PVC - 95mm² to 300mm²

Description

11kV 3 core stranded aluminium mains power cable is most suitable for use in power networks. For installation underground, outdoors and in cable ducting. Please note: the red outer sheath can be prone to fading when exposed to UV rays.

Key Features
  • Voltage Rating
    Voltage Rating 6.35/11kV Tested To Voltage And Duration of BS 6622
  • Minimum Bending Radius
    Minimum Bending Radius 12 x Overall Diameter
  • Flame Retardancy
    Flame Retardancy BS EN 60332-1-2
  • Temperature Limits
    Temperature Limits Maximum conductor operating temperature: 90°C
    Initial temperature at S.C.C for metallic screen: 80°C
    Maximum conductor temperature during short circuit: 250°C
Construction
  • Conductor: Class 2 Aluminimum conductors according to EN 60228
  • Conductor Screen: Bonded semi conductive material
  • Insulation: Cross Linked polyethylene (XLPE)
  • Insulation Screen: Strippable Extruded Semi Conductor
  • Screen: Each core copper tape screened
  • Tape: Semi-conducting tape insulated
  • Bedding: Polyvinyl Chloride (PVC)
  • Armour: Steel Wire Armour (SWA)
  • Outer Sheath: Polyvinyl Chloride (PVC)
  • Sheath Colour: Red
Standards
  • BS6622
  • IEC 60502-2
  • BS EN/IEC 60332-1-2
  • BS EN/IEC 60228

Core Colours

3 core - Brown Black Grey Tape