BS6622 3 Core Mains Cable 11kV - CU, XLPE, SWA, PVC - 25mm² to 400mm²

Description

Suitable for energy networks such as power stations. For installation in ducts, underground and outdoor. Please note: Red outer sheath can be prone to fading when exposed to UV rays.

Key Features
  • Voltage Rating
    Voltage Rating 6.35/11kV Tested To Voltage And Duration of BS 6622
  • Minimum Bending Radius
    Minimum Bending Radius 12 x Overall Diameter
  • Flame Retardancy
    Flame Retardancy BS EN 60332-1-2
  • Temperature Limits
    Temperature Limits Maximum conductor operating temperature: 90°C
    Initial temperature at S.C.C for metallic screen: 80°C
    Maximum conductor temperature during short circuit: 250°C
Construction
  • Conductor: Class 2 stranded copper conductor
  • Conductor Screen: Bonded semi conductive material
  • Insulation: Cross Linked polyethylene (XLPE)
  • Insulation Screen: Strippable Extruded Semi Conductor
  • Metallic Screen: Individual or overalapped copper tape screen
  • Bedding: Polyvinyl Chloride (PVC)
  • Armour: Steel Wire Armour (SWA)
  • Outer Sheath: Polyvinyl Chloride (PVC)
  • Sheath Colour: Red or Black
Standards
  • BS6622
  • IEC 60502-2
  • BS EN/IEC 60332-1-2
  • BS EN/IEC 60228

Core Colours

3 Core

Brown Black Grey Tape