BS7835 3 Core Armoured Mains Cable 11kV - XLPE, SWA, LSZH - 35mm to 400mm

Description
The 11KV Medium Voltage British Standard cable is suitable for installation in power networks, underground and in cable ducting. Its low smoke zero halogen sheath makes it suitable for installations where fire, smoke emissions and toxic fumes create a potential threat.
Please note: Due to poor UV resistant qualities, red outer sheath cables are not recommended for outdoor installation.
Key Features
-
Installation Guidelines Should not be installed at temperatures below 0°C or above +60°C
-
Voltage Rating 6350/11000 Volts
Tested To Voltage And Duration of BS7835 -
Minimum Bending Radius As Per Manufacturers Datasheet
-
Temperature Limits Ambient Temperature: -15°C to + 90°C
Construction
-
Conductor: Stranded Plain Annealed Compacted Circular Copper Conductor
-
Insulation: Cross Linked polyethylene (XLPE)
-
Bedding: LSZH (Low smoke Zero Halogen)
-
Metallic Screen: Individual or overalapped copper tape screen
-
Sheath: Low Smoke Zero Halogen (LSZH)
-
Separator: Copper Tape with 10% overlap
-
Armour: Galvanised Steel Wire Armour (SWA)
-
Sheath Colour: Red or Black
Standards
-
BS7835, BS EN50268 (IEC 61034), Flame propagation to BS EN 50265, BS EN 50266 (IEC 60332)
Core Colours
Brown, Black, Grey Tapes
Electrical Data
Maximum conductor operating temperature: 90°C
Maximum screen operating temperature: 80°C
Maximum conductor temperature during S.C: 250°C
Laying Conditions At Trefoil Formation Are As Below
Soil thermal resistivity: 120˚C. Cm/Watt, Burial depth: 0.5m ,Ground temperature: 15°C ,Air temperature: 25°C, Frequency: 50Hz